16 AS302P Single Phase Smart Meter
____________________________________________________________________
© Honeywell - M450 001 1D - 23.05.2019
Tariff Structure
The script defines the rates to turn ‘On’ or turn ‘Off’ at a particular time.
11.2.2. Tariff Switching Table
The Tariff supports a maximum of 200 Switching Points. These can be used in any combination over the maximum
number of Seasons/Week/Day Profiles given below.
11.2.3. Seasons
Up to 4 Seasons may be specified and at least one Season must be
programmed for the TOU Registers to be available.
The old Season ends at the instant the new Season starts.
A new Season starts at 00.00 of the specified date.
Start dates are specified as absolute (dd.mm) dates.
The example in the diagram shows four Seasons. Season 1 is in operation from
January to February, Season 2 from March to May, Season 3 from June to
September, Season 4 from October to December.
The Season Profile defines which week profile is active through that period.
11.2.4. Week Profile
A Week Profile allows different Day Profiles to be specified for each day of the week.
There is a maximum of 4 Week Profiles.
A minimum of one Week Profile is required for tariff operation.
A Day Profile is required to be defined for each day of the week.