8.2 PARAMETERS COMMON TO ALL PROGRAMS (GLOBAL)
Parameter
Message
Display
Function Available Settings (Lower Main Display)
Start On Defines setpoint value at the
start of each program.
Current setpoint value
Current process
variable value
End On Defines setpoint value at the
end of each program.
Final SP value
1
Controller SP value
Delay Time Defines delay (in
hours/minutes) between
initiating the program and
the program actually
starting.
Numerical value, with the decimal
point acting as the de-limiter
between the two units
(hours.minutes)
Program
Lock
Defines whether the operator
is permitted to change
program definitions whilst a
program is running/held.
Not permitted
Permitted
Power Fail
Recovery
Defines response to
restoration of power after
power failure.
0.00 or 1.00 if no Real Time Clock.
0.00 or Time (0.01 - 24.00) if Real
Time Clock fitted.
0.00 = Cold Start
2
1.00 or Time = Warm Start
3
RTC Time
4
Defines Real Time Clock
initial setting (hours.minutes).
0.10 - 24.00
RTC Day
4
Defines Real Time Clock
initial setting (day of week)
Sun , Mon , tuE , Wed , thu , Fri or SAt
External
Selection
Defines functions which may
be controlled externally
No external selection
Program selection
only
Only Run, Hold, Abort
and x60 functions
All program selection
and run control
functions
Lock
Code
5
Lock Code for Program
Define Mode
0 - 9999. Default = 10.
8-2
Program Number = A Segment Number = Blank
1 The final setpoint value for the End Marker of each program - see Subsection 8.4
2 Cold Start = Base Mode with Program No. as when power failed and Segment No. blank
3 Warm Start = resumption from point when power failed (with RTC, if Time has not
expired, otherwise Cold Start.
4 Available only if Real Time Clock fitted.
5 Only applicable if instrument is configured to have two lock codes.