Cable Types
The unit must be wired to the L
ONWORKS network using
either
level IV 22 AWG (Belden part number 9D220150)
or
plenum-rated level IV 22 AWG (Belden part number
9H2201504) non-shielded, twisted-pair, solid-
conductor wire.
When possible, use Honeywell AK3781, AK3782, AK3791,
or AK3792 cable (US part numbers). See Excel 50/5000
L
ONWORKS Mechanisms, EN0B-0270GE51, for details,
including maximum lengths.
Use wire with a minimum size of 20 AWG (0.5 mm
2
) and a
maximum size of 14 AWG (2.5 mm
2
).
termination
module
XL Web XL Web
11 11
55
66
12 12
Fig. 13. Connection to L
ONWORKS network and
termination module (here: daisy-chain network
configuration)
The Excel Web controller can be connected to the
L
ONWORKS network via terminals 5+6 and 11+12 of the
removable terminal plug or via the L
ONWORKS jack (see
also section "LonWorks " on page 3).
This permits individual Excel Web controllers to be
connected / disconnected from the L
ONWORKS network
without disturbing the operation of other devices.
Depending upon the chosen network configuration, one or
two terminations may be required.
Two different L
ONWORKS termination modules are
available:
L
ONWORKS termination module, order no.: 209541B
L
ONWORKS connection / termination module
(mountable on DIN rails and in fuse boxes),
order no.: XAL-Term
3
4
L
O
N
H
o
n
e
y
w
e
l
l
X
A
L
-
T
e
r
m
L
O
N
removable screw-type
3-pole terminal block
15
34
06
shield shield
LON
Ter min ation
FTT/LPT Bus
FTT/LPT Free
Park Position
plug-in
jumper
Fig. 14. L
ONWORKS connection and termination module
BINARY INPUT AND OUTPUTS
Wiring
When wiring the two binary outputs and the binary input,
use a min. size of 20 AWG (0.5 mm
2
) and a maximum of
14 AWG (2.5 mm
2
). The max. length of all cables is 400 m.
Two wires with a total thickness of 14 AWG can be twisted
together and connected using a wire nut (include a pigtail
with this wire group and attach the pigtail to the individual
terminal block). Deviations from this rule can result in
improper electrical contact. Local wiring codes may take
precedence over this recommendation.
Binary Input
The Excel Web controller's binary input (a normally-open
contact) is not galvanically isolated. It is suitable for con-
nection with / signalling via 0...36 Vdc voltage or external
resistor or dry contact.
purpose assigned to
binary input by user
using CARE 7.0
vol-
tage
at
binary
input
resist. at
binary con-
tact (ext.
resistor or
dry con-
tact)
info
high-level detection (i.e.
detection that binary
input has opened)
3.8 to
36 Vdc
> 10 k or
open input
voltage at
open ter-
minals =
5 V
low-level detection (i.e.
detection that binary
input has closed)
0.8 to
0 Vdc
< 400 k or
when binary
input
shorted
current from
shorted
terminals =
2 mA
The binary input is protected against miswiring. Specifically,
it is protected against voltages of up to 29 Vac; when
miswired, the Excel Web controller is unable to detect a
valid input signal.
Binary Outputs
The Excel Web controller is equipped with two binary
outputs.
Hardware Limits
A min. current of 50 mA is required to ensure a reliable
contact.
The binary outputs are designed for a max. continuous
current of 2 A.
Switching voltage = 24 Vac ± 20%.
NOTE: If inductive components are to be connected to
the binary outputs and if these binary outputs
switch more often than once every two minutes,
these components must be prevented from
causing harmful interference to radio or television
reception (conformance with EN 45014).
ENGINEERING, COMMISSIONING
Please refer also to CARE 7 User Guide (Product
Literature No.: EN2B-0182GE51) for more information.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel Web XL1000A and is the answer not in the manual?

Honeywell Excel Web XL1000A Specifications

General IconGeneral
BrandHoneywell
ModelExcel Web XL1000A
CategoryController
LanguageEnglish

Related product manuals