28 IFP-FFT Manual — P/N 54708:B3 10/28/2021
System Operation JumpStart Operation
6.2.8 Zone Active
Each zone has an Active LED (see Figure 6.1). The Zone's Active LED will illuminate when a remote handset is plugged into that zone. The
LED will turn off when the handset is removed from the zone.
6.2.9 Zone Trouble
Each zone has a Trouble LED (see Figure 6.1). The Trouble LED will blink when specific SLC issues occur, such as a missing device or
double address. Pressing the Silence key will cause the Zone Trouble LED to turn on solid. Once the zone trouble is corrected, the LED will
turn off.
6.3 JumpStart Operation
The JumpStart feature will attempt to locate all SLC mini-monitor modules installed in the system, indicate all devices found on the FFT and
FFT-24, and allow the user to accept the configuration, repeat the JumpStart process, or allow the configuration to be discarded. To run
JumpStart:
1. Press and hold the JumpStart button for 2 seconds.
2. The FFT will search for installed SLC devices and activate the Active LEDs of all zone/point addresses found.
3. After JumpStart is complete, the first four status LEDs will blink.
4. Press the ACCEPT key to save the configuration. The FFT will restart. Or, press the JumpStart key again to repeat the SLC search
process.
5. If you do not press the Accept key within one minute after JumpStart completion, the configuration will be discarded and the FFT will
restart.
Answer LED
Active LED (green)
Trouble LED (amber)
Figure 6.1 LED Operations