FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Table 3-32 Water quality requirements
Conductivity rate at 20°C
(σ
20
)
a
a: When σ
20
is less than 300 μS/cm, the first vapor exhausting duration of the humidifier is
long; when σ
20
greater than 1250 μS/cm, the humidifier service life is affected.
3.3.2.3 Technical Specifications
Table 3-33, Table 3-34, and Table 3-35 describe the NetCol5000-C technical specifications.
Table 3-33 NetCol5000-C technical specifications (1)
NetCol5000-C030H6B2010020
E1
NetCol5000-C030H6B201002
0E0
220 V AC, 1 Ph, 50 Hz/60 Hz
Tolerance: –10% to +10% of
rated voltage, rated frequency±3
Hz, one active power supply, and
one standby power supply
220 V AC, 1 Ph, 50 Hz/60 Hz
Tolerance: –10% to +10% of
rated voltage, rated frequency±3
Hz, one active power supply,
and one standby power supply
Maximum
operating pressure
Configuration of a
condensate pump
Configuration of an
air deflector
⚫
For a 1000 mm deep model:
no
⚫
For a 1200 mm deep model:
optional