FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Table 3-58 lists the temperature sensor specifications.
Table 3-58 Temperature sensor specifications
3.4.11 Multi-Functional Sensor
A multi-functional sensor integrates the smoke sensor and temperature and humidity (T/H)
sensor and can connect to the ECC800 controller system over PoE or wireless
communication.
Figure 3-65 shows a multi-functional sensor.
Figure 3-65 Multi-functional sensor
Specifications
Table 3-59 lists the multi-functional sensor technical specifications.
Table 3-59 Multi-functional sensor technical specifications
–40°C to +80°C, precision ≤ ±0.5°C (0–50°C)
0–100% RH, precision ≤ ±5% RH (25°C, 20%–80% RH)
Complies with Ul217. The smoke sensor generates an alarm when
testing 3.2% weak dust for each foot.