FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
One PoE port that complies with IEEE802.3AT
One DI input port, 12 V DC power input
Wireless communication:
⚫
Press the button for less than 1s to start blinking.
⚫
Hold down the button for 1–5 seconds to search for a network and
start networking.
⚫
Hold down the button for more than 6 seconds to clear network
parameters.
Indicators
Table 3-60 describes the indicators on the multi-functional sensor.
Table 3-60 Description of the indicators on the multi-functional sensor
Module
running status
indicator
The power supply is normal.
The power supply is abnormal.
Blinking at
long intervals
The multi-functional sensor
successfully registers with the
ECC800 and the software runs
properly (the indicator blinks at 0.5
Hz, on for 1s and then off for 1s).
Blinking at
short intervals
The multi-functional sensor fails to
register with the ECC800 or the
communication fails (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
The indicator blinks at super short
intervals for 0.5s (blinking at 10
Hz, on for 0.05s and then off for
0.05s) and then turns off for 0.5s.
The cycle lasts for 10s.
A system failure alarm or smoke
alarm is generated.