7 Man-Machine Interaction
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Special User has logged in to the
SUN2000.
6. Set Ugrid-Unbalance, 10-min Over-Volt,
and 10-min OV Prot. time, and press .
The parameters displayed vary with the setting
of Grid Code.
----End
7.2.11 Setting Isolation Parameters
SUN2000 isolation parameters can be set on the monitoring panel.
Context
If PV strings are grounded, install a three-phase four-wire isolation transformer and set
Isolation to Input Grounded, With TF.
Procedure
The following table lists the procedure for setting isolation parameters. The parameter
values in the figures are for reference only.
1. On the default screen, press to enter
the main menu.