UPS2000-G-(6 kVA-20 kVA)
User Manual
Copyright © Huawei Technologies Co., Ltd.
Torqu
e for
Tighte
ning
Bolts
16 mm
2
M6 90°
OT
terminal
220 V AC,
230 V AC,
or 240 V
AC
125 A
(the
characte
ristics of
D)
20 kVA
(three-phas
e input
three-phase
output)
380 V AC,
400 V AC,
or 415 V
AC
63 A
(the
characte
ristics of
D)
16 mm
2
M6 90°
OT
terminal
380 V AC,
400 V AC,
or 415 V
AC
63 A
(the
characte
ristics of
D)
If customers purchase input and output power cables by themselves, use the cables that comply with
standards proposed by Underwriters Laboratories (UL) or International Electrotechnical
Commission (IEC).
Two-mains-input scenarios are not supported on the UPS2000-G-15 kVA/20 kVA (single-phase
input single-phase output).
3.1.4 Unpacking and Checking
Figure 3-4 shows the transportation safety requirements.