121
Updated
28/02/01
1. Data provided by APC.
2. How-to-Read example for 220-240(208): Input VAC is 220- 240 as is the UPS output when electric service is active. When electriic service is interupted and the UPS is on battery the UPS output is 208 VAC.
3. Battery output may be set to 220, 225, 230, or 240 VAC.
4. Two PDU jumper cables ship with the UPS for attachment from the IEC 320-C19 receptacles to Power Distribution Units (PDU) (P/N 2PDUxxx).
5. SU-5000RMiB (P/N 37L6862) contains a Terminal Block (TB) for direct attachment to an electrical source by qualified personnel.
6.Where ‘xx’ represents the appropriate country code as follows:- 14=UK, 15=Denmark/Switzerland, 16=EUR, 17=Israel, 18=Italy, 19=South Africa.
7. Where ‘xxx’ represents the appropriate country code as follows:- DEN=Denmark, ISR=Israel, ITA=Italy, SDI=Saudi Arabia, SAF=South Africa, SWS=Switzerland, UKM=United Kingdom, EUR=Europe.
Total Configuration Runtime Estimator (Time in minutes)
1
Tower Rack Mount
EMEA
Part Number
SU-700iNET
P/N SUP072Y
SU-1000iNET
P/N SUP102Y
SU-1400iNET
P/N SUP144Y
SU-2200iNET
P/N 06P60xx
5
SU-1400RMiB
P/N 14RIxxx
6
SU-3000RMiB
P/N 30RIxxx
6
SU-5000RMiB
P/N 37L6862
US
Part Number
SU-700NET
94G3134
SU-1000NET
94G3135
SU-1400NET
94G3136
Not Available SU-1400RMB
94G6674
SU-3000RMB
94G6676
SU-5000RMB
37L6861
Total Load (Watts) Runtime Minutes
Runtime Minutes Runtime Minutes Runtime Minutes Runtime Minutes Runtime Minutes Runtime Minutes
200 22 38 62 130 45 104 240
250 17 28 43 104 34 84 200
300 12 22 34 85 25 70 166
350 9 18 29 71 22 58 145
400 7 14 23 65 18 52 125
450 5 12 20 52 15 45 110
500-11184313 3897
550 - 9 16 38 11 35 87
600 - 8 13 34 10 31 76
650 - 7 12 31 9 29 68
700 - 6 11 28 8 26 63
750 - - 10 25 8 24 59
800 - - 9 23 7 22 55
850 - - 8 21 7 20 51
900 - - 7 19 6 18 47
950 - - 6 18 5 17 43
1000 - - - 17 - 16 39
1100 - - - 15 - 14 34
1200 - - - 13 - 12 31
1300 - - - 11 - 10 28
1400 - - - 9 - 9 25
1500 - - - 9 - 8 22
1600 - - - 8 - 8 20
1700 - - - - - 7 18
1800 - - - - - - 17
1900 - - - - - - 14
2000 - - - - - - 12
2100 - - - - - - 11
2200 - - - - - 11
2300 - - - - - - 10
2400 - - - - - 10
2500 - - - - - - 9
2600 - - - - - 9
2700 - - - - - - 8
2800 - - - - - - 8
1. Data provided by APC.
Steps:
1. Identify the devices contained in the configuration.
2. Sum the load (watts) of all devices in the configuration. Use either Maximum Load for minimum runtime, or Typical Load for typical runtime.
3. Find the Total Configuration Load in the table above.
4. Select the most appropriate UPS model to achieve the desired runtime.
5. Where ‘xx’ represents the appropriate country code as follows:- 14=UK, 15=Denmark/Switzerland, 16=EUR, 17=Israel, 18=Italy, 19=South Africa.
6. Where ‘xxx’ represents the appropriate country code as follows:- DEN=Denmark, ISR=Israel, ITA=Italy, SDI=Saudi Arabia, SAF=South Africa, SWS=Switzerland, UKM=United Kingdom, EUR=Europe.
NOTE: If the Total Configuration Load is greater than the entries above, split the load across two or more UPS units.