28
Function
Code
Parameter name Setting Range
Unit
Default
Commission
43: PID parameter switchover
44: User defined fault 1
45: User defined fault 2
46: Speed control/Torque control switchover
47: Emergency stop
48: External STOP terminal 2
49: Deceleration DC braking
50: Clear the current running time
51: Switchover between two-line mode and
three line mode
52 to 59 : Reserved
F4-10 DI filter time 0.000 to 1.000
Sec
0.010
F4-11 Terminal command mode 0 : Two-line mode 1
1 : Two-line mode 2
2 : Three-line mode 1
3 : Three-line mode 2
N.A
0
F4-12 Terminal UP/DOWN rate 0.01 to 65.535
Hz/s
1.00
F4-13 AI curve 1 minimum input 0.00 to F4-15 V
0.00
F4-14 Corresponding setting of
AI curve 1 minimum input
-100.00 to 100.00
%
0.0
F4-15 AI curve 1 maximum input F4-13 to 10.00V
Volt
5.00
F4-16 Corresponding setting of
AI curve 1 maximum
input
-100.00 to 100.00
%
100.0
F4-17 AI 1 filter time 0.00 to 10.00
Sec
0.10
F4-38 DI valid mode selection
(for DI1 to DI5)
00000 to 11111 (binary)
N.A
00000
F4-39 DI valid mode selection 2
(for DI6 to DI10)
00000 to 11111 (binary)
N.A
00000