Commissioning and Trial Run
‑129‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
U5‑54 30006 Expansion card 2 ‑ AI1
function
0–65535 0 ‑ Modification
prohibited
U5‑55 30007 Expansion card 2 ‑ AI2
function
0–65535 0 ‑ Modification
prohibited
U5‑56 30008 Expansion card 3 ‑ AI1
function
0–65535 0 ‑ Modification
prohibited
U5‑57 30009 Expansion card 3 ‑ AI2
function
0–65535 0 ‑ Modification
prohibited
U5‑60 30012 Power supply unit ‑
AI1 voltage
0–65535 0 ‑ Modification
prohibited
U5‑61 30013 Power supply unit ‑
AI2 voltage
0–65535 0 ‑ Modification
prohibited
U5‑62 30014 Expansion card 1 ‑ AI1
voltage
0–65535 0 ‑ Modification
prohibited
U5‑63 30015 Expansion card 1 ‑ AI2
voltage
0–65535 0 ‑ Modification
prohibited
U5‑64 30016 Expansion card 2 ‑ AI1
voltage
0–65535 0 ‑ Modification
prohibited
U5‑65 30017 Expansion card 2 ‑ AI2
voltage
0–65535 0 ‑ Modification
prohibited
U5‑66 30018 Expansion card 3 ‑ AI1
voltage
0–65535 0 ‑ Modification
prohibited
U5‑67 30019 Expansion card 3 ‑ AI2
voltage
0–65535 0 ‑ Modification
prohibited
4.6 List of Fault Codes
The following faults may occur during the use of the AC drive. Troubleshoot the faults
according to the solutions described in the following table.
Table 4–3 Fault codes
Fault Name Panel
Display
Possible Cause Solution Fault Type
STO product model
identification error
E01.06 Hardware fault Check the AC drive nameplate to confirm
whether the AC drive has the STO function. If
not, contact the technical support
personnel.
Axis fault
AC drive axis type
identification setting
error
E01.07 Hardware fault Check the AC drive nameplate to confirm the
axis type (single‑axis or dual‑axis) of the AC
drive.
Axis fault