Commissioning and Trial Run
‑38‑
4.5 List of Parameters
Table 4–1 Power supply unit parameters
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F0‑01 61441 Product SN 800.0 800 ‑ Modification
prohibited
F0‑02 61442 Software version 0.00–655.35 0.00 ‑ Modification
prohibited
F0‑03 61443 Temporary software
version
0.00–655.35 0.00 ‑ Modification
prohibited
F0‑04 61444 Customized SN 0–9999 0 ‑ Modification
prohibited
F1‑00 61696 Bus undervoltage
threshold
Single‑phase 220 V:
150–220 V
Three‑phase 380 V:
300–440 V
Single‑phase
220 V: 190 V
Three‑phase
380 V: 350 V
V Modifiable
in any states
F1‑01 61697 Bus overvoltage
threshold
Single‑phase 220 V:
300–410 V
Three‑phase 380 V:
600–820 V
Single‑phase
220 V: 410 V
Three‑phase
380 V: 820 V
V Modifiable
in any states
F1‑02 61698 Braking unit applied
voltage
Single‑phase 220 V:
300–410 V
Three‑phase 380 V:
600–820 V
Single‑phase
220 V: 750 V
Three‑phase
380 V: 370V
V Modifiable
in any states
F1‑03 61699 Braking transistor
open circuit enable
0: Disabled
1: Enabled
1 ‑ Modifiable
in any states
F1‑04 61700 Braking transistor
short circuit enable
0: Disabled
1: Enabled
1 ‑ Modifiable
in any states
F1‑05 61701 Input phase loss
enable
0: Disabled
1: Enabled
2: Alarm
2 ‑ Modifiable
in any states
F1‑06 61702 Input overvoltage
enable
0: Disabled
1: Enabled
2: Alarm
2 ‑ Modifiable
in any states
F1‑07 61703 Fan fault enable 0: Disabled
1: Enabled
2: Alarm
1 ‑ Modifiable
in any states
F1‑08 61704 Reserved 0–1 1 ‑ Modification
prohibited
F1‑09 61705 Fan control 0: Running in one direction
1: Forward and reverse
running
0 ‑ Modifiable
in any states