Goodrive20-EU series VFD Function parameters
70
Detailed instruction of parameters
Displayed
parameters 2
of running state
0x0000 – 0xFFFF
BIT0: analog AI1 value (V on)
BIT1: analog AI2 value (V on)
BIT2: analog AI3 value (V on)
BIT3: high speed pulse HDI frequency
BIT4: motor overload percentage (% on)
BIT5: the VFD overload percentage (% on)
BIT6: ramp frequency given value (Hz on)
BIT7: linear speed
BIT8: AC inlet current (A on)
BIT9 – 15: reserved
The parameter
selection of the
stop state
0x0000 – 0xFFFF
BIT0: set frequency (Hz on, frequency flickering
slowly)
BIT1: bus voltage (V on)
BIT2: input terminals state
BIT3: output terminals state
BIT4: PID reference (% flickering)
BIT5: PID feedback value (% flickering)
BIT6: torque reference (% flickering)
BIT7: analog AI1 value (V on)
BIT8: analog AI2 value (V on)
BIT9: analog AI3 value (V on)
BIT10: high speed pulse HDI frequency
BIT11: PLC and the current step of multi-step
speed
BIT12: pulse counters
BIT13 – BIT15: reserved
Frequency
display
coefficient
0.01 – 10.00
Displayed frequency=running frequency* P07.08
Speed display
coefficient
0.1 – 999.9%
Mechanical rotation speed =120*displayed
running frequency×P07.09/motor pole pairs
Linear speed
displayed
coefficient
0.1 – 999.9%
Linear speed= Mechanical rotation
speed×P07.10