Goodrive20-EU series VFD Function parameters
94
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
0: Detect all the time
1: Detect during constant running
Setting range of P11.09: P11.11 200%
Setting range of P11.10: 0.1 3600.0s
LED thousands:
Overload integral function selection
0: Overload integral is invalid;
1: Overload integral is valid
P11.11
Underload
pre-alarm
detection level
If the VFD current or the output current is lower
than P11.11, and its lasting time is beyond
P11.12, the VFD will output underload pre-alarm.
Setting range of P11.11: 0 P11.09
Setting range of P11.12: 0.1 3600.0s
50%
P11.12
Underload
pre-alarm
detection time
1.0s
P11.13
Output terminal
action selection
during fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x00 0x11
LED ones:
0: Action during undervoltage fault
1: No action during undervoltage fault
LED tens:
0: Action during the automatic reset period
1: No action during the automatic reset period
0x00
P11.14
Speed
deviation
detection value
0.0 50.0%
Set the speed deviation detection time.
10.0%
P11.15
Speed
deviation
detection time
This parameter is used to set the speed deviation
detection time.
Actual detecting
value
t1
t2
DEu
In running
Fault output
Speed
t1t2, so the VFD continues running
t2=P11.15
Setting range of P11.15: 0.0 10.0s
0.5s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive20-EU VFD Series and is the answer not in the manual?

INVT Goodrive20-EU VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive20-EU VFD Series
CategoryDC Drives
LanguageEnglish

Related product manuals