Basic Operation
4. Power on the three instruments separately.
After the instrument is restarted, the VFD shows that the instrument is work-
ing in single mode.
5.11 Digital I/O Function (Digital Port)
This series power supply supports digital I/O function. The user can realize logic
control over signal input or output by related configurations in the system menu.
Pins Introduction
Different I/O implements different functions. The detailed functions description
are shown in the figure below:
Pin Type
Description (Default function)
Properties
1 Input/Output Ps-Fault-Clear, clear the protec-
tion state.
Pulse signal
2 Input/Output Ps, protection state indicator. Level signal
3 Input/Output Off-Status, OnOff-status
indicator.
Level signal
4 Input/Output Trig(in), trig signal. Pulse signal
5 Input/Output INH-Living, Turn off the output
under emergency status.
Pulse signal
6 Input/Output Sync-On, synchronous on
control.
Pulse signal
7 Input/Output Sync-Off, synchronous off
control.
Pulse signal
GND Ground terminal, that is, the negative terminal
corresponding to each of the above 7 pins.
Level signal
Copyright © Itech Electronic Co., Ltd.
140

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ITech IT-M3900C Series and is the answer not in the manual?

ITech IT-M3900C Series Specifications

General IconGeneral
BrandITech
ModelIT-M3900C Series
CategoryPower Supply
LanguageEnglish

Related product manuals