Step 1: Prepare the Site for MX5, MX10, MX40, or MX80 Installation
MX5, MX10, MX40, and MX80 Router Rack Requirements on page 4
Tools Required to Prepare the MX5, MX10, MX40, and MX80 Router for
Installation on page 5
Move the Mounting Brackets for Center-Mounting the MX5, MX10, MX40, or MX80
Router, If Needed on page 5
MX5, MX10, MX40, and MX80 Router Rack Requirements
You can install the router in a four-post rack or cabinet or an open-frame rack.
The rack rails must be spaced widely enough to accommodate the router chassis's
external dimensions: 3.5 in. (8.9 cm) high, 21.75 in. (55.2 cm) deep, and 17.4 in. (44.2 cm)
wide. The outer edges of the mounting brackets extend the width to 19.2 in. (48.7 cm).
The rack must be strong enough to support the weight of the fully configured router,
up to 30 lb (13.6 kg).
For the cooling system to function properly, the airflow around the chassis must be
unrestricted. Allow at least 6 in. (15.2 cm) of clearance between side-cooled routers.
Allow 2.8 in. (7 cm) between the side of the chassis and any non-heat-producing
surface such as a wall.
For service personnel to remove and install hardware components, there must be
adequate space at the front and back of the router. Allow at least 30 in. (76.2 cm) in
front of the router and 24 in. (61 cm) behind the router.
The rack or cabinet must have an adequate supply of cooling air.
Ensure that the cabinet allows the chassis hot exhaust air to exit from the cabinet
without recirculating into the router.
The router must be installed into a rack that is secured to the building structure.
Mount the router at the bottom of the rack if it is the only unit in the rack.
When mounting the router in a partially filled rack, load the rack from the bottom to
the top with the heaviest component at the bottom of the rack.
Copyright © 2015, Juniper Networks, Inc.4
MX5, MX10, MX40, and MX80 3D Universal Edge Router Quick Start

Other manuals for Juniper MX5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper MX5 and is the answer not in the manual?

Juniper MX5 Specifications

General IconGeneral
BrandJuniper
ModelMX5
CategoryNetwork Router
LanguageEnglish

Related product manuals