User manual wM-Bus Dongle SW Tool
Appendix C: Flonidan Rev. B meter set-up
5512-1057 GB / 12.2011 / A1
Figure 10
If the option board (radio module) in the meter is an old Flonidan Revision B type, the set-up should
be as follows:
• Transfer the data from the Main tab, or enter the METER ADDRESS manually.
• Set the options as shown, i.e. tick the checkboxes Meter enabled, 2-way radio, Rev B
compatible and Meter data valid (Options in hex = 23).
• If the meter is not installed, set the Meter Install state to 255. Next time the meter sends out an
ACCESS DEMAND INSTALL STATE (Ci=0x06), the Dongle will acknowledge this, and the state will
change to 1 when seeing the next message from the meter.
• Set Meter M-Bus address to where you want the meter to respond on the M-Bus.
• T1 period and T2 fraction cannot be set.
• IEK and KEY are not used.
• Set the Rev B barcode. As this is not included in the radio message, the Dongle will add this to
the wired M-BUS REQ_UD2 response.
• The Option Board data fields are not used.
13