31
GB
Operation of the Unit
2.2 Parameter Summary
Display Parameter Adjust. range Resolution
Factory setting
CP. 0 Password input 0...9999 1 -
CP. 1 Actual frequency display - 0,1 Hz -
CP. 2 Inverter status display - - -
CP. 3 Actual load - 1 % -
CP. 4 Peak load - 1 % -
CP. 5 Rated frequency 0...409.58 Hz 0.0125 Hz 50.0 Hz
CP. 6 Boost 0...25.5 % 0.1 % 2 %
CP. 7 Acceleration time 0.01...300 s 0.01 s 10 s
CP. 8 Deceleration time 0.01...300 s 0.01 s 10 s
CP. 9 Minimal frequency 0...409.58 Hz 0.0125 Hz 0 Hz
CP.10 Maximal frequency 0...409.58 Hz 0.0125 Hz 70 Hz
CP.11 Fixed frequency 1 0...±409.58 Hz 0.0125 Hz 5 Hz
CP.12 Fixed frequency 2 0...±409.58 Hz 0.0125 Hz 50 Hz
CP.13 Fixed frequency 3 0...±409.58 Hz 0.0125 Hz 70 Hz
CP.14 Max. ramp current 10...200 % 1 % 140 %
CP.15 Max. constant current 10...200 % 1 % 200 %
CP.16 Speed search 0...15 1 8
CP.17 Voltage stabilization 150...649 V,off 1 V off
CP.18 Slip compensation -2.50...2.50 0.01 0=off
CP.19 Autoboost -2.50...2.50 0.01 0=off
CP.20 DC-braking 0...9 1 7
CP.21 Braking time 0...100 s 0.01 s 10 s
CP.22 Relay output 0...xx 1 2
CP.23 Frequency value 0...409.58 Hz 0.0125 Hz 4 Hz
CP.24 Reference signal (only C) 0...2 1 0
Password
FUNC
ENTER
UP
Releasing the
CP-Parameter
FUNC
ENTER
UP
Password
Barring the
CP-Parameter
2.3 Password Input Ex works the frequency inverter is supplied without password protection,
this means that all changeable parameters can be adjusted. After
parameterizing the unit can be barred against unauthorized access. The
adjusted mode is stored.