35
GB
Operation of the Unit
2.6 Special
Adjustments
The following parameters serve to optimize the drive and adaption onto
certain applications. These adjustments can be ignored at the initial startup.
This function protects the frequency inverter against switching off by
overcurrent during the acceleration ramp. When the ramp reaches the
adjusted value here, then it is stopped so long until the current decreases
again. CP.2 displays "LAS" at active function.
Adjustment range:10...200 %, 200%=oFF up to case D
10...200%; >150% = oFF from case E
Resolution: 1 %
Factory setting: 140 %
Customer adjustment: _______ %
This function protects the frequency inverter against switching off due to
overcurrent during constant output frequency. When exceeding the
adjusted value here, the output frequency is reduced until the value drops
below the adjusted value. CP. 2 displays "SSL" at active function.
Adjustment range:10...200 %, 200%=oFF up to case D
10...200%; >150% = oFF from case E
Resolution: 1 %
Factory Setting: 200 %
Customer adjustment: _______ %
Max. ramp current
Max. constant current
t
f
set
f
real
on
off
on
off
C.15
C.14
LAD-stop
Current limit
t
t
t
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Other manuals for KEB COMBIVERT F4-C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F4-C and is the answer not in the manual?

KEB COMBIVERT F4-C Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F4-C
CategoryDC Drives
LanguageEnglish

Related product manuals