Technical Data
©
2020 KEB America, Inc.
15
4.1.3 Electrical Operating Conditions
4.1.3.1 Device Classification
Requirement
Standard
Class
Description
Overvoltage category
EN 61800-5-1
III
-
EN 60664-1 III -
Pollution degree
EN 60664-1
II
Non-conductive pollution, occasional
concensation when PDS is out of service
Table 3: Device classification
4.1.3.2 Electromagnetic Compatibility
EMC Emitted
Interference
Standard Class Description
Conducted emissions EN 61800-3 C2 -
Radiated emissions
EN 61800-3
C2
-
Immunity
Standard
Level
Description
Static discharges EN 61000-4-2 8kV
4kV
AD (air discharge)
CD (contact discharge)
Burst Port for process
measurement control
lines and signal interfaces
EN 61000-4-4
2kV
-
Burst Power ports
EN 61000-4-5
4kV
-
Surge Power ports EN 61000-4-5 1kV
2kV
Phase-phase
Phase-ground
Immunity to conducted
disturbances induced by
radio-frequency fields
EN 6100-4-6 10V 0.15 to 80 MHz
Electromagnetic fields EN 61000-4-3 10V/m
3V/m
1V/m
80 MHz to 1 GHz
1.2 to 2 GHz
2 to 2.7 GHz
Table 4: Electromagnetic compatibility

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5
CategoryDC Drives
LanguageEnglish

Related product manuals