Handle of poisonous engine oil, fuel, cooling water and battery, please refer to the related
provision.
Periodic check as per running record
Establish the running record for daily operation, maintenance and check.
Periodic check is divided into several intervals like 50 hours, 250 hours, 500 hours, 750 hours
and 1000 hours.
7.1 Check period
Check for initial 50 hours:
Replace engine oil
Replace engine oil filter element
Check the fan belt tension
Check for every 250 hours:
Replace engine oil
Replace engine oil filter element
Clean air cleaner
Measure insulation resistance of the generator.(Once for a month)
Check specific gravity of the battery electrolyte.
Check for every 500 hours:
Replace the fuel filter element
Clean the radiator
Check the electrical circuit terminal & wiring connector
Cooperating with the check every 250 hours.
Check for the 1000 hours
Clean inner part of the fuel tank
Replace air cleaner element
Adjust fuel injection time
Check anti-vibration rubber
Check the nylon tube & rubber tube
Check sound absorber
Cooperate with the check every 250 hours and check every 500 hours.
Refer to engine operation manual for the details