TP-7044 6/23 43
FMI
(Failure Mode
Indicator)
Event ID/Parameter at Local Display
Level
Alarm
Horn
Fault
Lamp
Programmed
Input
Programmed
Output
High
Engine Coolant Temperature *
Shutdown
On
Red
AD
D
Open Circuit
Engine Coolant Temperature *
Shutdown
On
Red
D
Shorted High (3)
Engine Coolant Temperature *
Shutdown
On
Red
D
Shorted Low (4)
Engine Coolant Temperature *
Shutdown
On
Red
D
High
Lube Oil Temperature *
Warning
On
Yellow
AD
High
Lube Oil Temperature *
Shutdown
On
Red
D
Low
Engine Coolant Level
Shutdown
On
Red
D
D
Low
Engine Fuel Level
Warning
On
Yellow
AD
D
Low
Engine Fuel Level
Shutdown
On
Red
D
D
High
Engine Fuel Level
Warning
On
Yellow
D
D
Critically High
Engine Fuel Level
Warning
On
Yellow
D
D
Low
Fuel Pressure
Warning
On
Yellow
AD
D
Low
Fuel Pressure
Shutdown
On
Red
AD
D
Low
Gen Battery Voltage
Warning
On
Yellow
D
High
Gen Battery Voltage
Warning
On
Yellow
D
Low
Cranking Voltage
Warning
On
Yellow
D
Low
Engine Oil Level
Warning
On
Yellow
AD
D
Low
Engine Oil Level
Shutdown
On
Red
D
D
Low
Generator Voltage L1-L2
Shutdown
On
Red
D
High
Generator Voltage L1-L2
Shutdown
On
Red
D
Low
Generator Voltage L2-L3
Shutdown
On
Red
D
High
Generator Voltage L2-L3
Shutdown
On
Red
D
Low
Generator Voltage L3-L1
Shutdown
On
Red
D
High
Generator Voltage L3-L1
Shutdown
On
Red
D
Low
Avg Gen Voltage L-L
Warning
On
Yellow
D
High
Avg Gen Voltage L-L
Warning
On
Yellow
D
Low
Generator Frequency
Warning
On
Yellow
D
High
Generator Frequency
Warning
On
Yellow
D
Low
Generator Frequency
Shutdown
On
Red
D
High
Generator Frequency
Shutdown
On
Red
D
Low
Total Power (Generator Total Real
Power)
Warning
On
Yellow
D
High
Total Power (Generator Total Real
Power)
Warning
On
Yellow
D
High
Total Power (Generator Total Real
Power)
Shutdown
On
Red
D
Low
Total Reactive Power
Warning
On
Yellow
D
High
Avg Current
Warning
On
Yellow
D
Low
Maximum Alternator Current
Shutdown
On
Red
D
High
Exhaust Temperature
Shutdown
On
Red
D
D
Low
Engine Seawater Pressure
Shutdown
On
Red
D
D
High
Intake Air Temperature
Warning
On
Yellow
D
High
Intake Air Temperature
Shutdown
On
Red
D
High
Fuel Temperature
Warning
On
Yellow
D
High
Fuel Temperature
Shutdown
On
Red
D

Table of Contents

Other manuals for Kohler 14EKOZD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 14EKOZD and is the answer not in the manual?

Kohler 14EKOZD Specifications

General IconGeneral
BrandKohler
Model14EKOZD
CategoryPortable Generator
LanguageEnglish

Related product manuals