TP-6198 3/1514 Section 1 Specifications
1.4 Torque Specifications
Follow the general torque specifications found in
Appendix C of this manual unless noted below or listed
in the engine service manual.
Torque Specifications
Alternator overbolts 34 Nm (25 ft. lb.)
Drive disk to flywheel 16.5 Nm (12 ft. lb.)
Cylinder head nuts 25 Nm (18 ft. lb.)
Drive disk to rotor 38 Nm (28 ft. lb)
Muffler flange bolts 50 Nm (35 ft. lb.)
Spark plug 25 Nm (18 ft. lb.)
Radiator fan fasteners 22.5 Nm (17 ft. lb.)
1.5 Alternator Specifications
Alternator Specifications
Frequency Hz
50 Hz (30 kW only)
or 60 Hz
Excitation method Brush type
Voltage regulator type Digital
Coupling type Flexible disc
Winding material Class H
Bearing, quantity and type 1 sealed
Circuit protection
Controller (F3) 10-amp fuse
Aux. winding (F1) 10-amp fuse
Relay Interface Board (F2) 10-amp fuse
Brush length, new 1.9 cm (0.75 in.)
Alternator Specification
15RES
15RESA
15REYG
15RYG
15REYG
15RYG
30REYG
30RYG
30REYG
30RYG
30RES
30RESA
30REYG
30RYG
30REYG
30RYG
Alternator model 4H7 4J7 2F5 2G5 2F7 2G7
Stator leads, qty. 4 12 4 12 4 12
Phase 1 3 1 3 1 3
Rotor resistance, ohms, cold 3.0 3.0 5.2 5.2 5.6 5.6
Stator resistance, ohms,* cold
Main winding: 1-2, 3-4 0.07 — 0.06 — 0.02 —
Main winding: 1-4, 2-5, 3-6, 7-10, 8-11, 9-12 — 0.04 — 0.09 — 0.06
Aux. winding: 55-66 1.26 1.3 0.60 0.19 0.44 0.18
Stator output AC voltage with separately excited
rotor using 12-volt battery, minimum:
Main winding: 1-2, 3-4 105 — 105 — 88 —
Main winding: 1-4, 2-5, 3-6, 7-10, 8-11, 9-12 — 120 — 140 — 112
Aux. winding: 55-66 130 150 140 190 117 150
Rotor field DC voltage/current readings at rated
output voltage, hot:
No load 16V/4.5A 16V/4.5A 19V/3.2A 12V/2.5A 19V/3.9A 15V/2.2A
Full load 36V/8.6A 40V/9.5A 51V/7.6A 63V/9.8A 53V/7.4A 69V/9.6A
* Most ohmmeters do not give accurate readings when measuring less than 1 ohm. The stator can be considered good if a low resistance
reading (continuity) is obtained and there is no evidence of shorted windings (discoloration). Do not confuse a low resistance reading with
a reading indicating a shorted winding.