TP-6198 3/1524 Section 2 Scheduled Maintenance
2.2.4 Battery Charger
Generator sets may be equipped with a factory-installed
battery charger to keep the starting battery fully
charged. Observe the battery polarity when connecting
the battery charger. Check the battery charger fuse and
power supply.
See the instruction sheet supplied with the battery
charger for information about battery charger operation
and troubleshooting.
2.3 Fuel System Maintenance
Routine fuel system service items include draining
water/sediment from piping at petcock or pipe end cap,
checking for fuel leakage at pipe connections, checking
flexible sections for cracking or chafing, and keeping
components clean including fuel regulator vent holes.
A grease or wax residue tends to accumulate in the
piping and fuel regulators over time. If fuel system
problems persist, disassemble the fuel system
components and check for residue buildup. Remove
any residue with a brush and mild detergent.