TP-6774 2/14a64 Section 7 Controller
Generator Set Calibration (User Defined). This
selectable display is in the GenSet Metering Menu
allowing the user to calibrate the controller and
generator set. Use the pushbutton/rotary selector dial to
navigate and select this feature.
Changes to this display must be done with the generator
set running. The local display shows Enter calib? No or
Yes. Select No to make no change. Select Yes to
calibrate the following values:
D VoltsL1--L2:x.xV
D VoltsL2--L3:x.xV
D VoltsL3--L1:x.xV
D Volts L1--N: x.x V
D Volts L2--N: x.x V
D Volts L3--N: x.x V
The user can individually calibrate the values above or
reset all of them. The local display Reset all calib? No or
Yes. Select No to make no changes and exit GenSet
Calibration. Select Yes to reset all of the values.
When calibrating voltage, the metered value and the
number being entered as the calibrated value must be
within 10% of the system operating voltage.
Measurement Units (User Defined). This selectable
display is in the GenSet System Menu allowing the user
to choose between Metric and English displays. Use the
pushbutton/rotary selector dial to navigate and select
this feature. Changes to this display can be done with
the generator set running or stopped. The local display
shows Meas Units: Metric or Meas Units: English.
Remote Start. This status indicates that the generator
set start circuit was closed from a remote location
allowing the engine to crank and run. The remote
location is typically a set of contacts on a transfer switch
or remote start switch. The local display shows Remote
Start Status.
System Ready. This status indicates that the generator
set is in the AUTO mode and available to start if the start
circuit is closed. The local display shows System
Ready.
System Timer Failed. This notice indicates that the
controller timer logic has failed to time out a designated
function. The local display shows TimerErrorNotice.
Voltage Regulator Adjustment (User Defined). This
feature is in the Voltage Regulator Menu allowing the
user to fine adjust the output voltage. Use the
pushbutton/rotary selector dial to navigate and select
this feature. Changes to this display must be done with
the generator set running. The local display shows
Enter volt reg? No or Yes. Select No to exit the voltage
regulator menu. Select Yes to change the local display
VR V olt Adj: xxx.x V.
7.11 Menu Displays
Use the Menu Summary List section after reading and
understanding the features of the pushbutton/rotary
selector dial. See Section 7.5.5, Digital Display.
The Menu Summary List provides a quick reference to
the digital display data. Some digital display data may
not be identical to your display due to generator set
application differences. The closed bullet items
represent main level data and the open bullet items are
sub-level data. The Menu Summary List indicates items
that are user selectable. Use SiteTecht software for
changing programmable information.
Section 7.13, Reviewing the Menu Displays, provides a
digital display menu overview and explains the
navigation using the pushbutton/rotary selector dial.

Table of Contents

Other manuals for Kohler 5EFKOD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 5EFKOD and is the answer not in the manual?

Kohler 5EFKOD Specifications

General IconGeneral
BrandKohler
Model5EFKOD
CategoryMarine Equipment
LanguageEnglish

Related product manuals