10 TT-1403 4/16
6 Reconnect Power
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
open the enclosure.
DANGER
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Reconnect power to the system.
1. Install the transfer switch enclosure door(s).
2. Reconnect power to the transfer switch.
3. Reconnect the generator set engine starting
battery, negative (--) lead last.
4. Reconnect power to the battery charger, if
equipped.
7 Programming and Operation
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
open the enclosure.
DANGER
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Remove the transfer switch enclosure door(s) to access
the programmable exerciser. Do not contact electrical
connections when programming the exerciser.
Note: A lithium battery provides 5 year backup power.
The timer can be programmed after installation
before reconnecting power to the transfer switch.
7.1 Setting the timer
The timer provides flexible timing for daily and/or weekly
programming. The single-channel timer combines
24 hour/7 day timing.
Each exercise period requires separate programming of
the ON and OFF time. Up to 8 on/off operations are
allowed for each day for a total of up to 56 switching
cycles per week.
Be sure to program an off cycle after every on cycle.
The minimum time setting is 1 minute.
Setting the current time and day
1. Slide RUN switch to left symbol of clock face.
2. Press the 1.7 button until the arrow points to
current day (1=Monday, 2=Tuesday, etc.). Press
the h (hour) and m (minute) buttons to set the
current time. Pay attention to the AM/PM indicator.
The PM indicator shows from noon to 11:59 p.m.
3. Slide the RUN switch to run. The clock colon
between the hours and minutes blinks when the
clock is running.
2
tt1403
1. AUTO switch
2. RUN switch
3. Number 1 indicates
single channel timer
4. Switch on indicator
(light bulb symbol)
5. Cycle number indicator
6. Skip indicator
7. Skip a day button
8. Minutes button, m
9. Hour button, h
10. Reset button
11. 1...7 day selection
button
12. Program button
13. AM/PM indicators
14. Day 1--7 indicators
1
14
78911
10
12
4
13
5
3
6
Figure 18 Timer Switches and Display