TT-1403 4/16 15
9.1.2 Wiring
Wiring must comply with the National Electrical Code
and applicable local codes.
Note: Check that the supply voltage matches the
voltage marked on the unit. Wiring to incorrect
voltage will void the warranty.
1. Verify that power has been disconnected as
described above.
2. Use the leads supplied with the kit to connect the
exerciser according to the wiring diagram in
Figure 23.
9.2 ATS Setup,
Exerciser GM39330
Set DIP switch #2 on the Accessory Board to select
loaded or unloaded programmed exercise runs. See
Figure 22 and Figure 23 for the location o f the DIP
switches on the accessory board.
D Set DIP switch #2 to the OFF position to run the
generator set without transferring the load. See
Figure 24, or
D Set DIP switch #2 to the ON position to start the
generator set and transfer the load during
programmed exercise runs. For peak shave
applications, set the DIP switch to the ON position.
DIP switch #2 does not affect the exercise period that is
set by pressing the Exercise button on the ATS
controller.
DIP Switch
OFF
(open)
ON
(closed)
2 Loaded Exercise Unloaded Loaded
Figure 24 Accessory Board DIP Switch Setting
9.3 Operating Instructions,
Exerciser GM39330
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
open the enclosure.
DANGER
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
The programmable exerciser must have power
connected in order to set the time and program the unit.
1. Install the transfer switch enclosure door(s).
2. Reconnect power to the transfer switch.
3. Reconnect the generator set engine starting
battery, negative (--) lead last.
4. Reconnect power to the battery charger, if
equipped.
5. Remove the transfer switch enclosure door(s) to
access the programmable exerciser. Do not
contact electrical connections when programming
the exerciser.