44
6 O
2
Trim
6.9.2 Available Correction Modes
6.9.2.1 CorrectionType1
Correction type 1 is used when correction is applied to a linear control element, e.g. to the fre-
quency converter’s setpoint for adjusting the combustion air blower’s speed. The correction is
directly added to or subtracted from the setpoint.
Correction mode: Effect to the setpoint axis
Fig. 6-2 Correction Type1
NOTICE
When switching on any O
2
correction you must ensure, that the combustion boundary values
are maintained even with the maximum possible correction (100%). For details see chapter
6.9.5 Checking the Combustion Limit Values.