59
7 Internal Burner Firing Rate Controller
7.13 Manual Control
You also may switch the ETAMATIC to "Manual Control" with the terminals. By short-circuiting
the PT 100 signal (e.g. bridge terminal 19 and 20) the burner firing rate controller is switched
off. The fuel/air ratio controller then directly follows the input at the default firing rate input. The
display shows LE instead of HA.
NOTICE
Only use manual control while monitoring the system.
7.14 Meaning of the Display
7.15 How to Adjust the Burner Firing Rate Controller
Only adjust the burner firing rate controller with the parameters.
press key "Manual" to move the regular firing rate input of the firing rate controller.
press the keys 2 and 3 to variegate the burner firing rate.
to cancel firing rate controller, press key "Manual" again
Display in "FIRING RATE" switch position
setpoint actual value regular firing
rate input
internal
firing rate
Display in mode "MANUAL"
regular firing
rate input
(via channel 1)
internal firing
rate
actual value