Page 4
506044−01 06/08
OUTDOOR
COIL
TO
HFC−410A
DRUM
LOW
PRESSURE
COMPRESSOR
SUCTION LINE
SERVICE VALVE
TXV
GAUGE MANIFOLD
HIGH
PRESSURE
LIQUID LINE
SERVICE VALVE
FILTER
DRIER
OUTDOOR UNIT
(Uncased Coil Shown)
Figure 4. Typical Manifold Gauge Connection Setup
SERVICE PORT
SERVICE PORT
CORE
TO OUTDOOR UNIT
STEM CAP
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
SERVICE PORT CAP
TO INDOOR
UNIT
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
Figure 5. Angle−Type Service Valve
(Back−Seated Opened)
1. Remove stem cap with a wrench.
2. Use a service wrench with a hex−head extension
(3/16" for liquid-line valve sizes and 5/16" for
suction-line valve sizes) to back the stem out
counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
S With Torque Wrench: Tighten finger tight and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2.
To Access Ball−Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized
wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and
tighten as follows:
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.
1. Remove stem cap with a wrench.
2. Use an appropriately sized wrench to open. To open
valve, rotate stem counterclockwise 90°. To close
rotate stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized to wrench turn an additional
1/12 turn clockwise as illustrated in figure 2.
BALL
(SHOWN
CLOSED)
SERVICE
PORT CORE
TO INDOOR UNIT
TO OUTDOOR UNIT
TO OPEN ROTATE STEM
COUNTERCLOCKWISE
90°.
SERVICE
PORT
SERVICE PORT
CAP
STEM
CAP
VALVE
STEM
OPEN TO LINE SET WHEN VALVE IS
CLOSED, TO BOTH LINE SET AND
UNIT WHEN VALVE IS OPEN.
TO CLOSE ROTATE
STEM CLOCKWISE 90°.
Figure 6. Ball−Type Service Valve

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Dave Lennox Signature Collection XC15 and is the answer not in the manual?

Lennox Dave Lennox Signature Collection XC15 Specifications

General IconGeneral
BrandLennox
ModelDave Lennox Signature Collection XC15
CategoryAir Conditioner
LanguageEnglish

Related product manuals