FILTERS
FLEXYII_WSHP-IOM-0909-E Page 58
F
ILTER REPLACEMENT
After opening the filter access panel, lift the filter retaining log.
The filters can then be removed and replaced easily by sliding the dirty filters out and clean ones in.
The CLIMATIC controller can monitor the pressure drop across the filter (If option fitted)
The following set points can be adjusted depeding on the installation.
“Airflow” in page 3411 = 25Pa by default
“No filter “ in page 3412 = 50Pa by default
“Dirty Filter” in page 3413 = 250Pa by default
The actual pressure drop measured accross the coil can be read on the Climatic Display DS50 in menu 2131
.
The following faults may be identified
-Fault code 0001 AIRFLOW FAILURE, if measured P across the filter and coil is below the value set in page 3411
-Fault code 0004 DIRTY FILTERS, if measured P across the filter and coil is above the value set in page 3413
-Fault code 0005 MISSING FILTERS, if measured P across the filter and coil is below the value set in page 3412
Be Careful: do the filters' fire classification's choice according to
the local regulations

Table of Contents

Other manuals for Lennox Fhm 170

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Fhm 170 and is the answer not in the manual?

Lennox Fhm 170 Specifications

General IconGeneral
BrandLennox
ModelFhm 170
CategoryHeat Pump
LanguageEnglish

Related product manuals