IOM FLEXY II 1007 E Page 50
PRESSURE ADJUSTMENTS ON HONEYWELL
PRESSURE REGULATING VAL VE TYPE VK 4125 P
Pressure regulator adjustment with 300mbar gas
supply:
- The Burner must run in High Heat mode for this check.
- Place the tube of theaccurate manometer on the Inlet
pressure port (Figure 15) of the Gas Regulating Valve after
hav ing loosened the screw by one turn
Check and adjust if necessary the valve Inlet pressure to
20.0mbar (G20) or 25.0mbar f or Groningen (G25) or
37.0mbar for propane (G31) after gas burner ignition
(f i g. 1 6 )
High Heat Injection Pressure Checks
Check and adjust if necessary the valve OUTLET pressure
to 10.4mbar (G 20) / 13.1mbar f or Groningen (G25) & 34.3
mbar f or propane (G31) (f ig. 17)
The out pressure m ust be m eas ured on the press ure tap
located on the gas injector support bar to avoid the
pressure drop due to the elbow after the v alve
Fig. 15
Fig. 17
Fig.16
HEATING
: GAS
BURNER 60 & 120kW
INLET
PRESSURE
MEASU RIN G
PORT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox FLEXY II Series and is the answer not in the manual?

Lennox FLEXY II Series Specifications

General IconGeneral
BrandLennox
ModelFLEXY II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals