BLOWER PERFORMANCE
G51MP−60C−090 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transi-
tion to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2835 1335 1495 2340 1105 1155 1800 850 895 1440 680 695
0.10 25 2785 1315 1475 2345 1105 1135 1805 855 865 1515 715 690
0.20 50 2715 1280 1435 2275 1075 1080 1825 860 845 1560 735 685
0.30 75 2620 1235 1380 2260 1065 1035 1840 870 825 1600 755 680
0.40 100 2550 1205 1350 2230 1055 1015 1845 870 815 1620 765 670
0.50 125 2450 1155 1305 2175 1025 990 1850 870 790 1615 765 655
0.60 150 2365 1115 1270 2130 1005 940 1830 865 775 1615 760 640
0.70 175 2240 1060 1205 2070 975 915 1815 855 760 1595 755 620
0.80 200 2185 1030 1190 1965 925 865 1775 840 745 1555 735 605
0.90 225 2015 950 1150 1820 860 820 1690 800 715 1440 680 580
NOTES All air data is measured external to unit without filter (not furnished field provided).
G51MP−60C−090 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Re-
turn Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2840 1340 1450 2345 1105 1105 1895 895 900 1515 715 700
0.10 25 2765 1305 1415 2365 1115 1080 1950 920 885 1580 745 700
0.20 50 2695 1270 1385 2345 1105 1050 1985 935 870 1620 765 695
0.30 75 2605 1230 1335 2315 1090 1030 1990 940 850 1645 775 690
0.40 100 2530 1195 1300 2265 1070 990 1990 940 825 1665 785 675
0.50 125 2420 1140 1260 2210 1045 955 1970 930 800 1675 790 665
0.60 150 2330 1100 1220 2145 1010 925 1930 910 775 1665 785 650
0.70 175 2250 1060 1190 2050 965 885 1875 885 745 1645 775 630
0.80 200 2135 1010 1140 2000 945 865 1810 855 715 1620 765 615
0.90 225 2030 960 1090 1885 890 830 1720 810 685 1560 735 590
NOTES All air data is measured external to unit without filter (not furnished field provided).
G51MP−60C−110 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transi-
tion to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.
External Static
Pressure
Air Volume / Watts at Different Blower Speeds
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2625 1240 1350 2310 1090 1080 1885 890 885 1515 715 700
0.10 25 2570 1215 1330 2325 1095 1060 1910 900 865 1575 745 700
0.20 50 2410 1135 1305 2285 1080 1035 1930 910 845 1620 765 690
0.30 75 2425 1145 1265 2230 1055 990 1925 905 825 1635 770 675
0.40 100 2335 1100 1220 2175 1025 950 1910 900 810 1640 775 660
0.50 125 2270 1070 1195 2120 1000 935 1895 895 785 1640 775 640
0.60 150 2170 1025 1155 2045 965 885 1860 875 765 1630 770 630
0.70 175 2110 995 1130 1950 920 855 1795 845 730 1590 750 610
0.80 200 2035 960 1090 1885 890 820 1745 825 705 1540 725 580
0.90 225 1900 895 1055 1760 830 780 1665 785 680 1470 695 565
NOTES All air data is measured external to unit without filter (not furnished field provided).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G51MP?48C?090 and is the answer not in the manual?

Lennox G51MP?48C?090 Specifications

General IconGeneral
BrandLennox
ModelG51MP?48C?090
CategoryFurnace
LanguageEnglish

Related product manuals