INSTALLER CONFIGURATION
Installer con guration de nes the thermostat operation and
allows to adapt it to the different types of plants and systems. To
access the con guration menu, simultaneously press the “
“ e
buttons for a few seconds until “COn” (con guration) appears
on the display.
Once entered in con guration menu, pressing “
“ scrolls through
the various parameters, identi ed with P and the parameter
number, from P01 to P24. The con guration end is displayed with
End”. Press “
“ again to save the con guration and and return to
normal operation.
Press the “
“ button, at any time, to exit from the con guration
menu without saving the changes.
When scrolling the parameters pressing button “
“ or
or
displays its current value.
To change the value, when it is displayed, press button
or
.
To prevent unauthorised access to the con guration remove the
internal jumper (JP5) shown in Fig. 6. Any attempt to access the
con guration will display the ashing
“ icon.
The installer con guration consists of two lists of parameters:
- main parameters P01 to P24 (table 1)
- extended parameters C01 to C19 (table 2)
The extended parameters C01-C19 allow an advanced thermostat
con guration.
When the display shows “COn“ at con guration start or “End“ at
con guration end, press the “
“ button to access the extended
parameters.
INSTALLER CONFIGURATION RESET
In order to reset the installer con guration, so that all parameters
are reset to the factory default values, enter the con guration
mode by holding down the keys “ “ and
until the display
shows “Con”, then hold down the two keys
and
for a few
seconds, until the display returns to the usual screen.
DESCRIPTION OF MAIN CONFIGURATION PARAMETERS
The main installer con guration parameters are shown in table 1
and explained below.
P01: System type selection.
2 pipes system: when con gured for a two-pipes system the
controller drives one valve only, wired at the “heating“ valve
terminals, both when heating and when cooling, as the same
valve is going to control either hot or cool water ow.
See wiring diagram in Fig. 8 a and b.
In case of a two-pipes system without valve, and therefore with no
wirings at the valve output terminals, make sure to set parameters
P03 and P04 to “fan control“ in order to get an effective regulation.
4 pipes system: when con gured for a four-pipes system the
controller drives both valves outputs in order to activate either the
hot water or the cooling one according to the actual requirements
of the controlled environment.
See wiring diagram in Fig. 8 c and d.
Electric heater system: the regulator is con gured to control a
system equipped with an electric heater: see the section “Electric
heater system” for more details.
Integrating electric heater system: the regulator is con gured to
control a system equipped with an electric heater: see the section
“Integrating electric heater system“ for more details.
Heat pump system: the regulator is con gured to control a system
equipped with a heat pump: see the section “Heat pump system“
for more details.
P02: This parameter sets the way how the controller switches from
the cooling mode (summer) to the heating mode (winter) and vice
versa.