Parameter setting
6-22
BA2131EN
6.6 Lenze-specific parameters
6.6.1 Only 82XX: Lenze parameter Operating Mode (L-C0001)
Parameter
name
(Index)
Sub-I
ndex
Data
str.
Data
type
Meaning
(Initialization is printed in bold)
Operating
mode
(5FFE
hex
)
0 S I32 Value Control source Setpoint source Parameter source
0 Terminal Terminal PROFIBUS
1 Terminal 8201 (keypad) PROFIBUS
2 Terminal Terminal PROFIBUS
3 PROF IBUS PROF IBUS PROF IBUS
6.6.2 Parameter L-C0142
This parameter L-C0142 prevents the drive from uncontrolled restarts after:
l
Mains connection and disconnection
l
Internal fault
l
Internal message (with pulse inhibit) > 0.5 s
If the controller sets the status Mesage“ because of an internal fault (e. g. short mains failure)and
the fault remains active longer than 0.5 s, the controller will be inhibited automatically.
The parameter L-C0142 has the following function:
l
L-C0142 = 1:
The controller restarts automatically as soon as the fault is not active any longer
l
L-C0142 = 0:
The controller remains inhibited and the drive cannot restart even if the fault is no longer
active.
The drive restarts after a LOW-HIGH transition at one of the inputs for Controller inhibit
(CHIN, e. g. at terminal X5/28)