Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Changing and saving parameters
3
21
EDKVF93−03 EN 2.0
3.1.4 Changing and saving parameters
Note!
Your settings have an effect on the current parameters in the main memory.
You must save your settings in a parameter set so that they are not lost when
the mains are connected.
If you only need one parameter set, save your settings as parameter set 1,
since parameter set 1 is loaded automatically after mains connection.
Step Key
sequence
Action
1. Select the menu ! " Use the arrow keys to select the desired menu
2. Change to the code level ! Display of the first code in the menu
3. Select code or subcode
Display of the current parameter value
4. Change to the parameter level
5. When SHPRG is displayed, inhibit the
controller
$
1)
The drive coasts
6.
Change parameter
A ! " Move cursor below the digit to be changed
B
Change of digit
Quick change of digit
7.
Accept the changed parameter
Display of SHPRG or SHPRG Confirm change to accept the parameter
Display "OK"
Display The parameter has been accepted immediately
8. Enable the controller, if required #
1)
The drive runs again
9.
Change to the code level
A Display of the operating level
B Display of the code with changed parameter
10. Change further parameters Restart the "loop" with step 1. or 3.
11.
Save changed parameters
A ! " Select the code C0003 "PAR SAVE" in the menu
"Load/Store"
B Change to the parameter level
Display "0" and "READY"
Select the parameter set in which
the parameters are to be saved
permanently
C
Save as parameter set 1:
ð Set "1" "Save PS1"
Save as parameter set 2:
ð Set "2" "Save PS2"
Save as parameter set 3:
ð Set "3" "Save PS3"
Save as parameter set 4:
ð Set "4" "Save PS4"
D When "OK" is displayed, the settings are permanently
saved in the selected parameter set.
12.
Change to the code level
A Display of the operating level
B Display of C0003 "PAR SAVE"
13. Set parameters for another parameter
set
Restart the "loop" with step 1. or 3.
1)
The function of the $ key can be programmed:
C0469 = 1: Controller inhibit
C0469 = 2: Quick stop (Lenze setting)
efesotomasyon.com - Lenze

Other manuals for Lenze 9300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 9300 Series and is the answer not in the manual?

Lenze 9300 Series Specifications

General IconGeneral
BrandLenze
Model9300 Series
CategoryController
LanguageEnglish

Related product manuals