Troubleshooting and fault elimination
System error messages
Resetting system error messages
4
43
EDKVF93−03 EN 2.0
RemedyCauseDescriptionFault message RemedyCauseDescription
DisplayNo.
0107 H07 Internal fault (power stage) During initialisation of the
controller, an incorrect power
stage was detected.
Contact Lenze.
x110 H10 Heatsink temperature sensor
error
Sensor for detecting the heatsink
temperature indicates undefined
values.
l Contact Lenze.
l Switch off the monitoring
(C0588 = 3).
x111 H11 Temperature sensor error:
Temperature inside the controller
Sensor for detecting the internal
temperature indicates undefined
values.
l Contact Lenze.
l Switch off the monitoring
(C0588 = 3).
0140 ID1 Error during motor data
identification.
No motor connected. Check motor connection.
Stator resistance too high. Check entered motor data.
Controller inhibited externally. Enable controller and repeat
motor data identification. The
controller enable must be
pending continuously until the
end of the identification process.
0141 ID2 Error during motor data
identification.
Motor too small. l Check entered motor data. For
parameterisation with Global
Drive Control, use the input
assistant for motor data.
l The measurements for the
inverter error characteristic
and the stator resistance are
correct (save measured values
in C0003). For the operating
mode V/f characteristic control
the motor data identification
can be completed.
Controller inhibited externally. Enable controller and repeat
motor data identification. The
controller enable must be
pending continuously until the
end of the identification process.
x200 NMAX Maximum system speed (C0596)
has been exceeded.
l Active load (e.g. for hoists) is
too high.
l Drive is not speed−controlled,
torque is excessively limited.
l Check drive dimensioning.
l Increase torque limit, if
necessary.
l Switch off monitoring
(C0607 = 3).
Representation of the error number:
x 0 = TRIP, 1 = message, 2 = warning
E. g. "2091": An external monitoring function has triggered EEr warning
4.5.2 Resetting system error messages
Response Measures for resetting the fault message
TRIP
Note!
If a TRIP source is still active, the pending TRIP cannot be reset.
Resetting the TRIP can be effected by:
l Pressing the keypad XT EMZ9371 BC ð $. Then press # to re−enable the controller.
l Setting code C0043 = 0.
l Control word C0135, bit 11
l Control word AIF
l Control word of system bus (CAN)
After resetting the TRIP, the drive remains at standstill.
Message
Danger!
After elimination of the fault, the fault message is cancelled automatically and the drive restarts
automatically.
Warning After elimination of the fault, the fault message is cancelled automatically.