Parameter data transfer
Writing parameters to the inverter
62
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3 Writing parameters to the inverter
Request header
Parameter attribute
Index and subindex
Note!
When a multi-parameter write request is processed, the parameter attribute, index,
subindex, and then the parameter format and parameter value are repeated "n" ti-
mes, "n" being the number of parameters requested.
A parameter request must not exceed the maximum data length of 240 bytes.
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Request identification Axis Number of indices
Field Data type Values
Request reference U8 This value is specified by the I/O controller.
Request identification U8 0x02: Write parameter
Axis U8 0x00 or 0x01
Number of indices U8 0x"n" (n = number of parameters requested)
Byte 5 Byte 6
Attribute Number of subindices
Field Data type Values
Attribute U8 0x10: Value
Number of subindices U8 0x00 or 0x01
Byte 7 Byte 8 Byte 9 Byte 10
Index Subindex
High byte Low byte High byte Low byte
Field Data type Values
Index U16 0x0001 ... 0xFFFF (1 ... 65535)
Subindex U16 0x0001 ... 0xFFFF (1 ... 65535)

Table of Contents

Other manuals for Lenze E84AYCER

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze E84AYCER and is the answer not in the manual?

Lenze E84AYCER Specifications

General IconGeneral
BrandLenze
ModelE84AYCER
CategoryControl Unit
LanguageEnglish

Related product manuals