Commissioning
Setting the IP configuration
38
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4 Setting the IP configuration
The IP configuration is required for addressing the Inverter Drive 8400 if communication between
the PC/»Engineer« or the IO controller and the inverter is to be established via PROFINET. This re-
quires the allocation of an IP address, subnet mask, and gateway address.
If no PROFINET network or IO controller is available yet, you can allocate the IP address, subnet
mask, and gateway address for the communication module by using the following options:
• Settings via the PROFINET configurator of the »Engineer«
( 40)
• Setting via codes in the »Engineer«
( 42)
Note!
• If the IP parameters are assigned by the IO controller via PROFINET or the PROFINET
configurator of the »Engineer«, changes become effective immediately and are saved
with mains failure protection.
• The assignment of invalid combinations of IP address, subnet mask, and gateway
address can have the consequence that no connection to the PROFINET can be estab-
lished.
• In the case of impermissible settings, the red LED BE (Fieldbus status displays
( 75))
blinks and the error message PROFINET: IP address error [0x01bc6533]
( 84) is out-
put.