Commissioning
Code Possible Settings
IMPORTANT
No. Name Lenze Selection
Password entry 0 0 999 Visible only when password is active
(see C94)
1
Setpoint source 0 Analog input (terminal 8; see C34)
1 Code c40 Observe notes about c40
2
Load Lenze setting 0 No action/loading complete
• C02 = 1... 4 only possible with
• C02 = 2 : C11, C15 = 60 Hz
1 Load 50 Hz Lenze settings
2 Load 60 Hz Lenze settings
3 Load OEM settings
4 Translate
WARNING!
C02 = 1... 3 overwrites all settings! TRIP circuitry may be disabled! Check codes
CE1...CE3.
NOTE
If an EPM that contains data from a previous software version is installed, C02 = 4
converts the data to the current version.
1
Configuration -
Digital Input E1
1 1 Activate xed setpoint 1 (JOG1)
• Use C37...C39 to adjust xed setpoints
• Activate JOG3: Both terminals =
HIGH
2 Activate xed setpoint 2 (JOG2)
3 DC braking (DCB) See also C36
4 Direction of rotation LOW = CW rotation
HIGH = CCW rotation
5 Quick stop Controlled deceleration to standstill,
active LOW; Set decel rate in C13 or c03
6 CW rotation
7 CCW rotation
CW rotation = LOW and CCW rotation =
LOW: Quick stop; Open-circuit protected
2
Configuration -
Digital Input E2
4
8 UP (setpoint ramp-up) UP = LOW and DOWN = LOW: Quick
stop; Use momentary NC contacts
9 DOWN (setpoint ramp-down)
10 TRIP set
Active LOW, triggers
(motor coasts
to standstill)
NOTE: NC thermal contact from the
motor can be used to trigger this input
Configuration -
Digital Input E3
3
11 TRIP reset See also c70
12 Accel/decel 2 See c01 and c03
13 Deactivate PI Disables PI function for manual control
14 Activate xed PI setpoint 1 • Use C37...C39 to adjust xed setpoints
• Activate xed PI setpoint 3: Both
terminals = HIGH15 Activate xed PI setpoint 2
Note
A fault will occur under the following conditions:
• E1...E3 settings are duplicated (each setting can only be used once)
• One input is set to UP and another is not set to DOWN, or vice-versa
4.3 Parameter menu