–125–
SUCTION ACCUMULATOR OPERATION
Liquid refrigerant collects in the suction accumulator
during the harvest cycle and is removed during the
freeze cycle. The liquid refrigerant is returned to the
compressor through a screen and orifice in the suction
accumulator J tube. Passing the liquid through the
orifice causes a pressure drop; the liquid flashes to a
vapor and creates a refrigeration affect. It is normal to
see frost on the accumulator, suction line and
compressor suction port in the freeze cycle. The
suction accumulator empties within the first 5 minutes
of the freeze cycle. When the refrigeration affect ends
(liquid refrigerant has been removed), the suction line
between the accumulator and compressor will
increase in temperature. The suction line temperature
increases 20 plus degrees two minutes after the liquid
has been removed. The time needed to remove the
liquid refrigerant will vary with the ambient
temperature and the length of the harvest cycle.
Higher ambient temperatures = shorter harvest cycles,
faster removal of liquid refrigerant from the
accumulator and greater suction line temperature
increases.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc CVD0675 and is the answer not in the manual?

Manitowoc CVD0675 Specifications

General IconGeneral
ModelCVD0675
TypeUndercounter Ice Maker
Ice TypeCube Ice
Weight240 lbs
Daily Ice Production675 lbs
Condenser TypeAir-Cooled
RefrigerantR-404A
Voltage208-230V
Ice Production675 lbs per day
Dimensions (H x W x D)38.5" x 24" x 28"
Production Capacity675 lbs per day
Power Supply208-230V, 60Hz, 1Ph

Related product manuals