–126–
REFRIGERANT CHARGE
Refrigerant charge on QuietQube ice machines is very
important. Overcharged or undercharged machines
will normally fail in the harvest cycle (produces even
sheets of ice, but will not harvest).
Undercharged ice machines run out of liquid
refrigerant in the receiver during harvest. This
increases the harvest cycle time and results in a
safety limit #2 failure.
Overcharged ice machines sub cool the liquid
refrigerant in the receiver during the freeze cycle,
resulting in a refrigerant boil off rate in the harvest
cycle that is too low. This increases the harvest
cycle time and results in a safety limit #2 failure.
When you are replacing refrigeration system
components, verify refrigerant charge is correct by
weighing amount recovered. Incorrect refrigerant
charge will result in component misdiagnosis.