158 Part Number STH025 11/16
SYMPTOM #3 REMOTE CONDENSER
Refer to Symptom
#2 - Freeze Cycle
Analysis Chart
Traditional Remote Ice Machine - Long Harvest/Low Production/Intermittent Safety Limit 2
Fails at night or in low
ambient - Operate
s
YES
YES
YES
NO
Liquid Line Temperature Cool
NO
e
Liquid Line
Temperature Warm
(body temperature)
Wet condenser
with water during
freeze cycle
Replace Headmaster
System low on refrigerant
Normal ice fill, long harvest cycle,
possible SL #2, back of cubes are
not melted at the end of harvest cycle
Discharge line temperature
is normal at the end of the
freeze cycle?
All Remotes = >150F/65C
START