LOCATION OF CVD CONDENSING UNITS
The location selected for the CVD Condensing Unit must
meet the following criteria. If any of these criteria are not
met, select another location.
The air temperature must be at least -20°F (-28.9°C)
but must not exceed 120°F (48.9°C).
The location must not allow exhaust fan heat and/or
grease to enter the condenser.
The location must not obstruct airflow through or
around the condensing unit. See below for clearance
requirements.
Minimum/Maximum Temperatures
Model
Minimum Air
Temperature
Maximum Air
Temperature
All Ice Machine
Head Sections
35°F
2°C
110°F
43°C
QuietQube
Condensing Units
CVDF0600
CVDF0900
CVDT1200
CVDF2100
-20°F
-29°C
120°F
49°C
CVDF1400
CVDF1800
-20°F
-29°C
130°F
54°C