Part Number 80-1505-3 6/11 193
ELECTRONIC BIN THERMOSTAT CONTROL
The temperature control opens the bin switch circuit
when ice contacts the sensor. When ice no longer
contacts the sensor, the circuit closes and the ice
machine starts.
SPECIFICATIONS
Setpoint Range: -30 to 212°F (-34 - 100°C)
CONTROL SETTINGS
Verify control is set properly before proceeding.
POSITIONING THE TOUCH PAD JUMPERS
P5 Jumper
The P5 jumper position determines if the touch pad is
locked or unlocked. The control is factory locked; to
unlock move the jumper from one pin to two pins.
Display Function Preset Settings
SP Set Point 40
DIF Differential 1
ASD Anti-Short Cycle
Delay
1
OFS Temperature
Offset
0
SF Sensor Failure
Mode
1