Part Number 80-1505-3 6/11 27
LOCATION OF CVD
®
CONDENSING UNIT
The location selected for the CVD Condensing Unit
must meet the following criteria. If any of these criteria
are not met, select another location.
CVD885/CVD1075/CVD1085/CVD1485/
CVD1885/CVD2085 Only - The air temperature
must be at least -20°F (-28.9°C) but must not
exceed 130°F (54.4°C).
CVD675/CVD685/CVD1185/CVD2075/CVD3085
Only - The air temperature must be at least
-20°F (-28.9°C) but must not exceed 120°F
(48.9°C).
CVD1486 Only- The air temperature must be at
least 50°F (10°C) but must not exceed 110°F
(43°C).
The location must not allow exhaust fan heat and/
or grease to enter the condenser.
The location must not obstruct airflow through or
around the condensing unit. See below for
clearance requirements.