Part Number 000014797 Rev02 05/18 131

UDE065 ice machines have a very small refrigerant charge
and we do not recommend diagnosing the ice machine
using refrigerant pressures. For this reason refrigeration
access fittings are not installed during production and the
ice machine is diagnosed with temperatures.
Verify that your water flow is even across the entire
evaporator before diagnosing the refrigeration system.
Mineral build-up on the evaporator assembly can cause
water tracking and an erratic ice fill pattern. Clean with
Manitowoc Ice Machine cleaner to remove any mineral
buildup before diagnosing the refrigeration system.
The following can be used for diagnostics:
1. Install a temperature lead on the compressor suction
line within 6” of the compressor.
2. Install a temperature lead on the compressor
discharge line within 6” of the compressor
3. Refer to the “Cycle Times, 24 Hr. Ice Production
and Refrigerant Pressure Charts” on page 217 to
determine the correct temperature operating range
for your air and water temperature.
4. Record the temperatures throughout the freeze and
harvest cycles.
NOTE: First cycle is not used for refrigeration system
diagnostics. Run a minimum of two cycles to allow the
system to stabilize and record the second cycle.

Table of Contents

Other manuals for Manitowoc URF0140A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc URF0140A and is the answer not in the manual?

Manitowoc URF0140A Specifications

General IconGeneral
BrandManitowoc
ModelURF0140A
CategoryIce Maker
LanguageEnglish

Related product manuals