Abnormal temperatures
Higher than normal freeze cycle temperatures.
A dirty filter or condenser will result in higher than
normal temperatures. Always clean the filter and
condenser before diagnosing the refrigeration system.
Hot water entering the ice machine will result in high
suction and discharge line temperatures in the freeze
cycle.
Capillary tube failures or low refrigerant charge will always
result in a starving evaporator.
An obstructed capillary tube or low refrigerant charge
will have a suction line temperature higher than
normal.
An obstructed capillary tube or low refrigerant charge
will have a discharge line temperature lower than
normal.
An obstructed capillary tube will not effect the
discharge line temperature during the harvest cycle.
A low freeze and discharge line temperature in the
freeze cycle with a normal harvest cycle discharge line
temperature indicates an obstructed capillary tube.
Low refrigerant charge will have both the suction and
discharge line temperatures lower than normal in the
freeze and harvest cycles.

Table of Contents

Other manuals for Manitowoc URF0140A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc URF0140A and is the answer not in the manual?

Manitowoc URF0140A Specifications

General IconGeneral
BrandManitowoc
ModelURF0140A
CategoryIce Maker
LanguageEnglish

Related product manuals