EasyManuals Logo
Home>McQuay>Controller>MicroTech II

McQuay MicroTech II Installation Manual

McQuay MicroTech II
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
IM 781-2 Page 27
Figure 22. Analog Input 4 to 20 mA Wiring
UI1
G
UI2
Shield
Stud in
enclosur
e
200' max
Shielded,
Cable
Range: 0-20 mA
4-20 mA
Self-powered
sensor
+
-
i
499 Ohm
(supplied with
UI1
G
UI2
Shield
Stud in
enclosur
e
200' max
Shielded,
Cable
Range: 0-20 mA
Controller-powered
sensor
+
-
i
499 Ohm
(supplied with
AO3
AO2
AO1
AV+
1. Flow Rate Sensor (UI 7)
A water flow rate sensor is used by the CSM in decoupled chiller sequencing control (primary/secondary systems) to
determine when the system capacity should be decreased by one stage. See Figure 7 through Figure 10 for the location of
the flow rate sensor mounted in the decoupler line. The flow rate sensor can also be mounted in the common supply water
line (after the decoupler line and before the first cooling load branch line). In this case, the CSM calculates the decoupler
line flow by subtracting the primary flow from the measured common supply water line reading.
Note that since flow is only measured in one direction, a uni-directional flow meter is sufficient. If the flow meter is
mounted in the decoupler line it must be sized to measure up to 150% of the evaporator flow rate of the largest chiller. If
the flow meter is mounted in the common supply line it must be sized to measure the total flow capacity of the cooling load
pumps.
When the flow rate from supply to return in the decoupler line is greater than the flow rate of the next chiller to be staged
off by more than the adjustable differential, the system capacity may be reduced by one stage.
2. Chilled Water Loop Differential Pressure Transducer (UI 8)
The chilled water loop differential pressure transducer is used when chilled water loop bypass valve control, sequencing
pump control, or variable speed pump control is required. See Figure 8, Figure 10, and Figure 11. A quality differential
pressure sensor should be selected since water hammer can occur within the loop.
When loop bypass valve control is used, the chilled water loop differential pressure transducer allows the CSM to modulate
a bypass valve as required to maintain an adjustable differential pressure setpoint using a PI (proportional-integral) control
loop.

Table of Contents

Other manuals for McQuay MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech II and is the answer not in the manual?

McQuay MicroTech II Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals